Sensor tolerances from ASHRAE Guideline 13

How close should a BAS reading be to your meter? These are the values many specifications use, with the source, and a plain note on what is not covered.

Free to read, print and share.

What Guideline 13 is

ASHRAE Guideline 13, "Specifying Building Automation Systems," is a guide that engineers use when they write a BAS specification. It is not a code. One of its tables lists how accurate a reported value should be, and many project specifications copy that table.

The numbers are end to end. They include the sensor's own accuracy, the controller's analog-to-digital conversion and any loss in transmission. So the fair test is to compare what the BAS shows with a reference meter held at the sensor.

The reporting accuracy values

From Table 1, "Reporting Accuracy," in Addendum g to ASHRAE Guideline 13-2007, shown in I-P units
Measured variableReported accuracy
Space temperature±1 °F
Ducted air temperature±1 °F
Outside air temperature±2 °F
Dew point±3 °F
Water temperature±1 °F
Delta-T±0.25 °F
Relative humidity±5% RH
Water flow±2% of full scale
Airflow, terminal units±10% of full scale, from 10% to 100% of scale
Airflow, measuring stations±5% of full scale
Airflow, pressurized spaces±3% of full scale
Air pressure, ducts±0.1 in. w.g.
Air pressure, space±0.01 in. w.g.
Water pressure, absolute and differential±2% of full scale
Electrical: amps, volts, watts, power factor±1% of reading, not counting utility meters
Carbon monoxide (CO)±5% of reading
Carbon dioxide (CO2)±50 ppm

Source: ASHRAE Addenda g, h and i to Guideline 13-2007 (ashrae.org). The guideline describes these as values for typical HVAC applications and notes that industrial and process work may need tighter accuracy. Check the current edition and your project specification before you sign off on a point.

Reading "percent of full scale"

Percent of full scale is based on the top of the sensor's range, not on the reading in front of you.

Percent of reading is different. ±1% of reading on 40 amps is ±0.4 amps.

How to check a point

  1. Put a reference meter at the sensor, in the same air or water the sensor sees.
  2. Let both readings settle. Averaging sensors need several readings across the coil, then an average.
  3. Read the BAS value at the same moment and write down both numbers.
  4. Compare the difference with the tolerance in the project specification, or with the table above when the specification points to Guideline 13.

Your reference meter has its own accuracy. A meter that is only good to ±1 °F can't prove a sensor is within ±1 °F, so record which meter you used.

Where the workbook and the app use field practice instead. Not every pass criterion in the Test Guide comes from Guideline 13. These are common field values, and they are labeled that way:

The project specification always wins over both lists.