Free resources · Checklist
11 fast troubleshooting checks
Eleven faults that show up on almost every startup, what usually causes them and the first thing to check.
Free to read, print and share.
Before you start
Look at the equipment before you look at the screen. Most of these come down to power, wiring, signal type or a setting, and the fastest path is to measure at the device.
Temp reads extremely low or high (e.g. −40 or 300+ °F)
- Likely causes
- Open or shorted sensor; wrong thermistor type configured; wiring on the wrong input
- Check first
- Measure resistance at the controller with the sensor disconnected and compare to the sensor's chart
Temp reads a few degrees off everywhere
- Likely causes
- Wrong sensor curve; lead resistance on a long run (matters for 1k RTDs, rarely for 10k thermistors); sensor in a bad location
- Check first
- Confirm the sensor type setting; compare at the sensor with a reference
AO commands but the device doesn't move
- Likely causes
- No actuator power; wrong signal type (0–10 V vs 2–10 V vs 4–20 mA); wiring reversed
- Check first
- Measure the output signal at the actuator, then the actuator supply
Valve or damper moves backward
- Likely causes
- Normally open device configured as normally closed; actuator direction switch
- Check first
- Check the device spec, actuator direction setting, and output reverse-acting option
BO commands but equipment won't start
- Likely causes
- HOA in Hand or Off; VFD not in Auto; safety circuit open; wired to the wrong relay contact
- Check first
- Check HOA and drive mode, then the safety chain, then NO vs NC contact
Status says running when it's off (or the reverse)
- Likely causes
- Current switch setpoint wrong; belt broken; status wired to the wrong input
- Check first
- Look at the equipment, then adjust or replace the current switch
Analog value scaled wrong
- Likely causes
- Range or units configured wrong; 0–10 V vs 2–10 V mismatch; wrong transmitter range
- Check first
- Compare the transmitter nameplate range to the BAS scaling
MS/TP devices drop offline or are intermittent
- Likely causes
- Duplicate MAC; missing or extra termination; baud mismatch; star wiring; shields grounded at both ends; Max Master too low
- Check first
- Check MAC addresses and termination first, then baud and wiring layout
Device won't discover on BACnet/IP
- Likely causes
- Wrong subnet or VLAN; duplicate device instance; BBMD or firewall blocking UDP 47808
- Check first
- Confirm IP settings and device instance, then the network path
Network point value is stale
- Likely causes
- COV not subscribed; poll rate too slow; device offline; wrong object mapped
- Check first
- Compare to the equipment display and check the poll or COV setting
Controller resets or loses program
- Likely causes
- Undersized or shared transformer; voltage sag on equipment start; failed backup battery
- Check first
- Measure supply voltage during equipment starts
Work safely. Follow your company's electrical safety and lockout rules, and the manufacturer's instructions, before opening panels or measuring live circuits.
Prefer paper? Download the one-page cheat sheet (PDF).