11 fast troubleshooting checks

Eleven faults that show up on almost every startup, what usually causes them and the first thing to check.

Free to read, print and share.

Before you start

Look at the equipment before you look at the screen. Most of these come down to power, wiring, signal type or a setting, and the fastest path is to measure at the device.

  1. Temp reads extremely low or high (e.g. −40 or 300+ °F)

    Likely causes
    Open or shorted sensor; wrong thermistor type configured; wiring on the wrong input
    Check first
    Measure resistance at the controller with the sensor disconnected and compare to the sensor's chart
  2. Temp reads a few degrees off everywhere

    Likely causes
    Wrong sensor curve; lead resistance on a long run (matters for 1k RTDs, rarely for 10k thermistors); sensor in a bad location
    Check first
    Confirm the sensor type setting; compare at the sensor with a reference
  3. AO commands but the device doesn't move

    Likely causes
    No actuator power; wrong signal type (0–10 V vs 2–10 V vs 4–20 mA); wiring reversed
    Check first
    Measure the output signal at the actuator, then the actuator supply
  4. Valve or damper moves backward

    Likely causes
    Normally open device configured as normally closed; actuator direction switch
    Check first
    Check the device spec, actuator direction setting, and output reverse-acting option
  5. BO commands but equipment won't start

    Likely causes
    HOA in Hand or Off; VFD not in Auto; safety circuit open; wired to the wrong relay contact
    Check first
    Check HOA and drive mode, then the safety chain, then NO vs NC contact
  6. Status says running when it's off (or the reverse)

    Likely causes
    Current switch setpoint wrong; belt broken; status wired to the wrong input
    Check first
    Look at the equipment, then adjust or replace the current switch
  7. Analog value scaled wrong

    Likely causes
    Range or units configured wrong; 0–10 V vs 2–10 V mismatch; wrong transmitter range
    Check first
    Compare the transmitter nameplate range to the BAS scaling
  8. MS/TP devices drop offline or are intermittent

    Likely causes
    Duplicate MAC; missing or extra termination; baud mismatch; star wiring; shields grounded at both ends; Max Master too low
    Check first
    Check MAC addresses and termination first, then baud and wiring layout
  9. Device won't discover on BACnet/IP

    Likely causes
    Wrong subnet or VLAN; duplicate device instance; BBMD or firewall blocking UDP 47808
    Check first
    Confirm IP settings and device instance, then the network path
  10. Network point value is stale

    Likely causes
    COV not subscribed; poll rate too slow; device offline; wrong object mapped
    Check first
    Compare to the equipment display and check the poll or COV setting
  11. Controller resets or loses program

    Likely causes
    Undersized or shared transformer; voltage sag on equipment start; failed backup battery
    Check first
    Measure supply voltage during equipment starts

Work safely. Follow your company's electrical safety and lockout rules, and the manufacturer's instructions, before opening panels or measuring live circuits.